item: 126087
The type PS1260 VSH XPress ProFlow static balancing valve has M-profile press connections and is a wide range balancing valve with shut off function and fixed orifice (FODRV). The fixed orifice allows fast and accurate flow measurements with fixed Kv-value while the robust grip handle provides easy control. The numeric position indicator and memory stop assures optimal adjustment to the design flow. Type PS1260 valves are part of the VSH XPress system and are availlable in sizes DN15-DN50.

potable water

heating

cooling
industry
commercial building

WRAS
label
value
label
d1
value
15.0
label
DN1
value
DN15
label
l1
value
62
label
z1
value
44
label
DN2
value
DN15
label
l2
value
62
label
z2
value
44
label
M
value
90
label
H
value
104
label
Y
value
38
label
V
value
64
label
U
value
26
label
a
value
55
item
Pegler Proflow Fixed Commissioning Valve ULF FF DN15 / 15
item number with gtin
126087 (05022050435569)
product number with gtin
126087 (05022050578419)
manufacturer
Aalberts integrated piping systems Ltd (Pegler)
size
15 (DN15) ULF
weight
0.57 kg
dimensions
153x90x118 mm
packaging
carton (1 pce)
color
brass
materials
brass (CW511L (lead-free))
finishing
none
shape
straight
connection type
press (M), press (M)
pressure rating (PN)
PN 16
sealing
EPDM
max operating pressure liquid
16 bar
min. medium temperature
30 °C
max medium temperature
110 °C
peak medium temperature
110 °C
Kvs-value
0.25
Kv-value
0.03 - 0.27
product group
valves (EPDM)
ETIM class
EC011463 Regulating valveHS code
84818099
brand
VSH
series
XPress ProFlow Static
product type
PS1260
UNSPS
40141609
label
value
label
etim-class
label
Housing material
value
Bronze
label
Material quality
value
CuZn38As (CW511L)
label
Surface protection
value
Untreated
label
Nominal diameter
value
DN 15
label
Outer pipe diameter
value
15mm
label
Outer pipe diameter (imperial)
value
0.59"
label
Connection 1
value
Press sleeve
label
With coupling connection 1
value
Yes
label
Connection 2
value
Press sleeve
label
With coupling connection 2
value
Yes
label
Article compression class
value
PN 16
label
Flange compression class
value
PN 16
label
Suitable for tap water
value
Yes
label
Suitable for hot tap water
value
Yes
label
Suitable for central heating water
value
Yes
label
Max. operating pressure
value
16bar
label
Max. operating pressure (imperial)
value
232.06psi
label
Medium temperature (continuous)
value
30°C - 110°C
label
Medium temperature (continuous) (imperial)
value
86°F - 230°F
label
Suitable for manual operation
value
No
label
Thermostatic
value
No
label
Hydraulic balance control
value
Static
label
With drain valve
value
No
label
With thermometer
value
No
label
With position indicator
value
Yes
label
Kv value
value
0.03m³/h - 0.27m³/h
label
Kvs value
value
0.25m³/h
label
Length of connection 1
value
62mm
label
Length of connection 1 (imperial)
value
2.44"
label
Working length connection 1
value
44mm
label
Working length connection 1 (imperial)
value
1.73"
label
Length of connection 2
value
62mm
label
Length of connection 2 (imperial)
value
2.44"
label
Working length connection 2
value
44mm
label
Working length connection 2 (imperial)
value
1.73"
label
Height operating element
value
38mm
label
Height operating element (imperial)
value
1.5"
label
Diameter handwheel
value
90mm
label
Diameter handwheel (imperial)
value
3.54"
label
Spindle angle
value
55°
label
Spindle angle (imperial)
value
2.17"
label
With insulation
value
No
carbon footprint (A-C) embodied carbon
2.76kgCO2e
data source
TM65
we are here to help
You can compare up to 2 products
You can compare up to 4 products